UPS Systems Sizing and Efficient Uninterruptible Power Supplies

UPS Systems Sizing and Efficient UninterruptibleReal and Apparent Power, and Load Power Factor
Power SuppliesMost loads are actually sized in Watts (or Kilowatts
Sizing uninterruptible power supplies and UPS systems– kW). This is known as the ‘real power’
is more important than ever today as an oversizedof a load. Rear panel rating plates on equipment
UPS system will lead to increased running costs andtypically lists their maximum Watt rating and these
and under-sizing can leave little enough load capacitycan be summed to provide an overall power
for future expansion. Correctly sizing a UPS system iscalculation.
also important for efficiency. Normally the lower theThe next approach in UPS sizing is to look at the
load on a UPS, the less efficient it will run and theAmps being drawn by a system and the mains
higher the running costs.power supply voltage (Vac) it is being powered from.
Sizing UPS systems is not a complex topic but it isCombining the two using the formula VxA=VA
one of increasing importance given the higher powerprovides the ‘apparent power’ measure or
Blade servers now found within datacenters and theVA (kVA = 1000VA).
rapid growth that IT systems can experience withinAs well as rear panel rating plates, manuals,
a short time frame.datasheets and online portals can also provide useful
UPS Systems Sizingspecification data sources for sizing information. Some
The optimum loading for any electronic system isUPS manufacturers also maintain equipment
80% of overall capacity. Loading a UPS system to 90databases that can be accessed by companies such
or 100% capacity is more than acceptable as well butas Critical Power Supplies to help assess a client’s
can introduce two weaknesses. The first is that itdemand.
leaves little room for expansion but more importantly,Real and apparent power are linked by a term known
an on-line UPS may be forced into bypass by smallas Power Factor (pf). If only the Watt rating is
surges in load demand.provided it is common practice to total this and then
This is a normal UPS safety feature (and one thatdivide the final sum by a power factor of 0.8 to give
protects the load) but it can expose the loadan overall kVA value. However, load power factors
momentarily, until the demand decreases, to thecan vary from anywhere between 0.5 and 1.0 (unity)
vagaries of the mains power supply itself. Mostand care must be taken with this approach. In
on-line UPS are capable of working for predeterminedaddition power factors can be ‘leading’ or
periods on overload and these are usually specified in‘lagging’ and sizing for three-phase loads and
terms of 110%, 125%, 150% and 200% of capacity.generators adds further levels of complication to the
However, the higher the overload, the less time thecalculation.
UPS will continue to power the load from its inverterTwo final considerations include runtime and
supply. Line interactive or standby UPS do notredundancy. The runtime or battery backup required
provide the same level of inherent safety as anwill influence overall system design, configuration,
on-line UPS and without a built-in automatic bypasslogistis and floor space requirements. For runtimes
facility, will generally shutdown after a short period onlasting several hours, it is a commonly adopted
overload.approach to use additional battery packs. For large
UPS Sizing Considerationsthree phase UPS this approach can be limited by
When sizing a UPS system it is important to startspace availability and budget. In such instances a
with a classification of the potential loads to bestandby generator can be more favorable.
protected:Business continuity is normally the primary driver for
- Critical Loads: are the IT, telecoms and and electricalinstalling a UPS solution. Resilience is a key factor that
systems that are critical to business continuity. Theyis driven by the levels of redundancy required.
can include Blade file servers, telecoms systems, PCs,Normally this is referred to as parallel redundancy or
storage devices, security and building managementN+X where X equates to the level required. For
systems. These systems may be so vital that it isexample, a 100kVA in an N+1 redundant configuration
important to power them through even long durationwould require two 100kVA UPS systems to be
mains power failures, which will affect the size of theinstalled, where one module alone could power the
UPS battery chosen – or even overall powerload if the other is removed out of service for
solution in terms of combining a UPS and generatormaintenance or develops a fault.
solution.Future expansion is off course a final factor to
- Essential Loads: are vital to the organisation but notconsider. It is normal practice to add a 20%
critical. These could include some lighting, heating andexpansion factor (multiply by 1.2). In addition, if the
ventilation systems. Some of these systems mayfuture electrical installation is allowed for, additional
well have their own emergency standby powerUPS modules could be installed to meet expansion at
facilities built-into them.a later date.
- Non-essential Loads: are the systems that areUPS sizing is a relatively straight forward process.
non-critical. A measure of their appropriateness forThe larger the load and system, the more complex
UPS protection is to consider their impact onthe calculations and considerations, especially in terms
day-to-day operations when removed (forof resilience and capacity. For assistance in sizing your
maintenance).loads, designing a resilient system and selecting a UPS
From the list of critical and essential loads calculationssystem, consider a Critical Power Supplies Site
can then made of the overall load size.Survey by one of our Power Protection consultants.